BSMJ Power Supply Capacitor
Expert Service
Modern Facilities
Power Quality Expertise
Broad Product Coverage
Email : sky@syelectric.net
Product Details
Scope of Use
Self-healing low-voltage shunt capacitors are suitable for low-voltage power systems operating at frequencies of 50Hz or 60Hz. They are primarily used to improve the power factor, reduce reactive power losses, enhance voltage quality, and increase transformer capacity. These capacitors are also recognized as the nation’s recommended top energy-saving product.
Working Conditions
After the capacitor is disconnected from power, it must be ensured that its residual voltage drops to 10% of the rated voltage before it can be put back into operation—this typically takes about 200 seconds. Therefore, the controller should be selected with features for re-energization and interlock timing. If a standard controller is used instead, a fast-discharge device must be installed. However, this restriction does not apply to equipment equipped with equipotential switches. The altitude should not exceed 2000 meters. The ambient temperature category is -25°C/C, with a minimum temperature of -25°C and a maximum temperature category C (not exceeding 50°C; the average temperature over any 24-hour period must remain below 40°C, while the annual average temperature should not surpass 30°C). Finally, capacitors must be operated under proper ventilation conditions. It is strictly prohibited to use them in enclosed, non-ventilated spaces.